CVE-2011-1565 HIGH

Directory traversal vulnerability in IGSSdataServer.exe 9.00.00.11063 and earlier in 7-Technologies Interactive Graphical SCADA System (IGSS) allows remote attackers to (1) read (opcode 0x3) or (2) create or write (opcode 0x2) arbitrary files via ..\ (dot dot backslash) sequences to TCP port 12401.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-22,

Products Affected

Vendor Product Version
7t igss *
CVE-2011-1566 HIGH

Directory traversal vulnerability in dc.exe 9.00.00.11059 and earlier in 7-Technologies Interactive Graphical SCADA System (IGSS) allows remote attackers to execute arbitrary programs via ..\ (dot dot backslash) sequences in opcodes (1) 0xa and (2) 0x17 to TCP port 12397.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-22,

Products Affected

Vendor Product Version
7t igss *
CVE-2011-1567 HIGH

Multiple stack-based buffer overflows in IGSSdataServer.exe 9.00.00.11063 and earlier in 7-Technologies Interactive Graphical SCADA System (IGSS) allow remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via crafted (1) ListAll, (2) Write File, (3) ReadFile, (4) Delete, (5) RenameFile, and (6) FileInfo commands in an 0xd opcode; (7) the Add, (8) ReadFile, (9) Write File, (10) Rename, (11) Delete, and (12) Add commands in an RMS report templates (0x7) opcode; and (13) 0x4 command in an STDREP request (0x8) opcode to TCP port 12401.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-119,

Products Affected

Vendor Product Version
7t igss *
CVE-2011-1568 HIGH

Format string vulnerability in the logText function in shmemmgr9.dll in IGSSdataServer.exe 9.00.00.11074, and 9.00.00.11063 and earlier, in 7-Technologies Interactive Graphical SCADA System (IGSS) allows remote attackers to cause a denial of service and possibly execute arbitrary code, as demonstrated using the RMS Reports Delete command, related to the logging of messages to GSST.LOG. NOTE: some of these details are obtained from third party information.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-134,

Products Affected

Vendor Product Version
7t igss *
CVE-2011-2214 HIGH

Unspecified vulnerability in the Open Database Connectivity (ODBC) component in 7T Interactive Graphical SCADA System (IGSS) before 9.0.0.11143 allows remote attackers to execute arbitrary code via a crafted packet to TCP port 20222, which triggers memory corruption related to an "invalid structure being used."

CVSS 2.0

Severity: HIGH

Problem Type: NVD-CWE-noinfo,

Products Affected

Vendor Product Version
7t igss 8
7t igss *
7t igss 9
CVE-2011-2959 HIGH

Stack-based buffer overflow in the Open Database Connectivity (ODBC) service (Odbcixv9se.exe) in 7-Technologies Interactive Graphical SCADA System (IGSS) 9 and earlier allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a crafted packet to TCP port 22202.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-119,

Products Affected

Vendor Product Version
7t igss 8
7t igss 7
7t igss 2.0
7t igss *
7t igss 6
7t igss 3.0
7t igss 5.0
7t igss 4.1
7t igss 5.1
CVE-2011-3339 MEDIUM

Cross-site scripting (XSS) vulnerability in the Admin Control Center in Sentinel HASP Run-time Environment 5.95 and earlier in SafeNet Sentinel HASP (formerly Aladdin HASP SRM) run-time installer before 6.x and SDK before 5.11, as used in 7 Technologies (7T) IGSS 7 and other products, when Firefox 2.0 is used, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors that trigger write access to a configuration file.

CVSS 2.0

Severity: MEDIUM

Problem Type: CWE-79,

Products Affected

Vendor Product Version
7t igss 7
safenet-inc sentinel_hasp_sdk *
safenet-inc sentinel_hasp_run-time *
CVE-2011-4050 MEDIUM

Buffer overflow in 7-Technologies (7T) Interactive Graphical SCADA System (IGSS) 9.0.0.11200 allows remote attackers to cause a denial of service via a crafted packet to TCP port 12401.

CVSS 2.0

Severity: MEDIUM

Problem Type: CWE-119,

Products Affected

Vendor Product Version
7t igss 9.0.0.11200
CVE-2011-4053 HIGH

Untrusted search path vulnerability in 7-Technologies (7T) Interactive Graphical SCADA System (IGSS) before 9.0.0.11291 allows local users to gain privileges via a Trojan horse DLL in the current working directory.

CVSS 2.0

Severity: HIGH

Problem Type: NVD-CWE-Other,

Products Affected

Vendor Product Version
7t igss 8
7t igss 7
7t igss 2.0
7t igss 9.0.0.11129
7t igss *
7t igss 6
7t igss 3.0
7t igss 9
7t igss 5.0
7t igss 4.1
7t igss 5.1
CVE-2011-4537 HIGH

Multiple buffer overflows in 7-Technologies (7T) Interactive Graphical SCADA System (IGSS) 9.0.0.11355 and earlier allow remote attackers to execute arbitrary code or cause a denial of service via a crafted packet to TCP port (1) 12397 or (2) 12399.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-119,

Products Affected

Vendor Product Version
7t igss *
CVE-2012-0223 HIGH

Untrusted search path vulnerability in 7-Technologies (7T) TERMIS 2.10 and earlier allows local users to gain privileges via a Trojan horse DLL in the current working directory, a different vulnerability than CVE-2012-0224.

CVSS 2.0

Severity: HIGH

Problem Type: NVD-CWE-Other,

Products Affected

Vendor Product Version
7t termis 2.0
7t termis *
CVE-2012-0224 HIGH

Untrusted search path vulnerability in 7-Technologies (7T) AQUIS 1.5 and earlier allows local users to gain privileges via a Trojan horse DLL in the current working directory, a different vulnerability than CVE-2012-0223.

CVSS 2.0

Severity: HIGH

Problem Type: NVD-CWE-Other,

Products Affected

Vendor Product Version
7t aquis *