Stack-based buffer overflow in the NetBiterConfig utility (NetBiterConfig.exe) 1.3.0 for Intellicom NetBiter WebSCADA allows remote attackers to execute arbitrary code via a long hn (hostname) parameter in a crafted HICP-protocol UDP packet.
CVSS 2.0
Severity: HIGH
Problem Type: CWE-119,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiterconfig | 1.3.0 |
Intellicom NetBiter WebSCADA devices use default passwords for the HICP network configuration service, which makes it easier for remote attackers to modify network settings and cause a denial of service. NOTE: this is only a vulnerability when the administrator does not follow recommendations in the product's installation documentation. NOTE: this issue was originally reported to be hard-coded passwords, not default passwords.
CVSS 2.0
Severity: HIGH
Problem Type: CWE-255,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiter_webscada_firmware | 3.13.0 |
| intellicom | netbiter_webscada_ws100 | * |
| intellicom | netbiter_webscada_firmware | 3.11.1 |
| intellicom | netbiter_webscada_firmware | 3.12.6 |
| intellicom | netbiter_webscada_firmware | 3.11.0 |
| intellicom | netbiter_webscada_firmware | 3.13.2 |
| intellicom | netbiter_webscada_firmware | 3.20.0 |
| intellicom | netbiter_webscada_firmware | 3.30.2 |
| intellicom | netbiter_webscada_firmware | 3.30.1 |
| intellicom | netbiter_webscada_firmware | 3.13.1 |
| intellicom | netbiter_webscada_firmware | 3.11.2 |
| intellicom | netbiter_webscada_firmware | 3.30.0 |
| intellicom | netbiter_webscada_ws200 | * |
| intellicom | netbiter_webscada_firmware | 3.12.4 |
Directory traversal vulnerability in cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to read arbitrary files via a .. (dot dot) in the page parameter, a different vulnerability than CVE-2009-4463.
CVSS 2.0
Severity: MEDIUM
Problem Type: CWE-22,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiter_webscada_ws100 | * |
| intellicom | netbiter_nb200 | * |
| intellicom | netbiter_nb100 | * |
| intellicom | netbiter_modbus_rtu-tcp_gateway_mb100 | * |
| intellicom | netbiter_webscada_ws200 | * |
| intellicom | netbiter_serial_ethernet_server_ss100 | * |
| intellicom | netbiter_easyconnect_ec150 | * |
Absolute path traversal vulnerability in cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to read arbitrary files via a full pathname in the file parameter, a different vulnerability than CVE-2009-4463.
CVSS 2.0
Severity: MEDIUM
Problem Type: CWE-22,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiter_webscada_ws100 | * |
| intellicom | netbiter_nb200 | * |
| intellicom | netbiter_nb100 | * |
| intellicom | netbiter_modbus_rtu-tcp_gateway_mb100 | * |
| intellicom | netbiter_serial_ethernet_server_ss100 | * |
| intellicom | netbiter_webscada_ws200 | * |
| intellicom | netbiter_easyconnect_ec150 | * |
cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to execute arbitrary code by using a config.html 2.conf action to replace the logo page's GIF image file with a file containing this code, a different vulnerability than CVE-2009-4463.
CVSS 2.0
Severity: HIGH
Problem Type: CWE-94,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiter_webscada_ws100 | * |
| intellicom | netbiter_nb200 | * |
| intellicom | netbiter_nb100 | * |
| intellicom | netbiter_modbus_rtu-tcp_gateway_mb100 | * |
| intellicom | netbiter_serial_ethernet_server_ss100 | * |
| intellicom | netbiter_webscada_ws200 | * |
| intellicom | netbiter_easyconnect_ec150 | * |
WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms have a default username and password, which makes it easier for remote attackers to obtain superadmin access via the web interface, a different vulnerability than CVE-2009-4463.
CVSS 2.0
Severity: HIGH
Problem Type: CWE-255,
Products Affected
| Vendor | Product | Version |
|---|---|---|
| intellicom | netbiter_webscada_ws100 | * |
| intellicom | netbiter_nb200 | * |
| intellicom | netbiter_nb100 | * |
| intellicom | netbiter_modbus_rtu-tcp_gateway_mb100 | * |
| intellicom | netbiter_webscada_ws200 | * |
| intellicom | netbiter_serial_ethernet_server_ss100 | * |
| intellicom | netbiter_easyconnect_ec150 | * |