MidnightBSD

Advisories for knx

CVE-2015-8299 HIGH

Buffer overflow in the Group messages monitor (Falcon) in KNX ETS 4.1.5 (Build 3246) allows remote attackers to execute arbitrary code via a crafted KNXnet/IP UDP packet.

CVSS 2.0

Severity: HIGH

Problem Type: CWE-119,

Products Affected

Vendor Product Version
knx ets 4.1.5
CVE-2021-36799 LOW

KNX ETS5 through 5.7.6 uses the hard-coded password ETS5Password, with a salt value of Ivan Medvedev, allowing local users to read project information. NOTE: This vulnerability only affects products that are no longer supported by the maintainer

CVSS 3.x

Source Score Severity Vector Exploitability Impact
nvd@nist.gov 8.8 HIGH CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H 2.0 6.0

CVSS 2.0

Severity: LOW

Problem Type: CWE-798,

Products Affected

Vendor Product Version
knx engineering_tool_software_5 *
CVE-2021-43575 LOW

KNX ETS6 through 6.0.0 uses the hard-coded password ETS5Password, with a salt value of Ivan Medvedev, allowing local users to read project information, a similar issue to CVE-2021-36799. NOTE: The vendor disputes this because it is not the responsibility of the ETS to securely store cryptographic key material when it is not being exported

CVSS 3.x

Source Score Severity Vector Exploitability Impact
nvd@nist.gov 5.5 MEDIUM CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N 1.8 3.6

CVSS 2.0

Severity: LOW

Problem Type: CWE-798,

Products Affected

Vendor Product Version
knx engineering_tool_software_6 6.0.0
CVE-2023-4346

KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

CVSS 3.x

Source Score Severity Vector Exploitability Impact
ics-cert@hq.dhs.gov 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H 3.9 3.6
nvd@nist.gov 7.5 HIGH CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H 3.9 3.6

Products Affected

Vendor Product Version
knx connection_authorization -